Quick Reference — Reclaimed vs Potable Make-up
Typical chemistry envelope across the two make-up categories. Site-specific values depend on source water and treatment train design.
Parameter | Potable | Typical Reclaimed | Engineering Impact |
TDS | 200–500 mg/L | 600–1,500 mg/L | Higher scaling potential at any given cycle |
Ammonia | < 0.5 mg/L | 1–10 mg/L | Copper corrosion, nitrification in tower basin |
Phosphate | < 0.5 mg/L | 2–8 mg/L | Ca-phosphate scale on hot tubes |
Organics (BOD/COD) | Low | Elevated | Biofilm growth, biocide demand |
Silica | Variable | Often elevated | Hard ceiling on cycles without dispersant chemistry |
Microbiological load | Low | Higher | Legionella, nitrifier, sulfate-reducer risk |
Chloramine residual | Controlled | Variable | Material compatibility, biocide interaction |